Specifications Table for 4MXS-F

4MXS68F3V1B 4MXS68F3V1B2 4MXS68F2V1B
Dimensions Unit Height mm 735 735 735
    Width mm 936 936 936
    Depth mm 300 300 300
Weight Unit kg 58 58 58
Compressor Type   Hermetically sealed swing compressor    
Operation range Cooling Ambient Min. °CDB   -10 -10
      Max. °CDB   46 46
  Heating Ambient Min. °CWB   -15 -15
      Max. °CWB   18 15.5
Sound pressure level Cooling Nom. dBA 48 48 48
  Heating Nom. dBA 49 49 49
Refrigerant Type   R-410A R-410A R-410A
  Charge kg 2.6 2.6 2.6
  Charge TCO2Eq 5.4 5.4 5.4
  GWP   2,087.5 2,087.5 2,087.5
Piping connections Additional refrigerant charge kg/m 0.02 (for piping length exceeding 30m)    
  Level difference IU - OU Max. m 15    
    IU - IU Max. m 7.5    
  Total piping length System Actual m 60    
Standard Accessories Installation manual 1 1 1
  Drain plug 1 1 1
  Reducer assembly 1 1 1
Power supply Phase   1~ 1~ 1~
  Frequency Hz 50 50 50
  Voltage V 230 230 230
Notes (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m
  (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases (3) - Contains fluorinated greenhouse gases
Compressor Type     Hermetically sealed swing compressor Hermetically sealed swing compressor
Piping connections Additional refrigerant charge kg/m   0.02 (for piping length exceeding 30m) 0.02 (for piping length exceeding 30m)
  Level difference IU - OU Max. m   15 15
    IU - IU Max. m   7.5 7.5
  Total piping length System Actual m   60 60