FHQ100CAVEB / RZQSG100L8V1B FHQ140CAVEB / RZQSG140L7V1B
Poff (Off mode) W 0.0  
Cooling Psb (Standby mode cooling) W 7.0  
  Cooling-=-Cooling cdc degradation cooling 0.25  
Seasonal efficiency (according to EN14825) Cooling Pdesign kW 9.50  
    Annual energy consumption kWh 592.692  
    Seasonal efficiency (according to EN14825)-=-Cooling-=-Seasonal efficiency according to en14825 cooling energy efficiency class 5.61  
    D Condition (20°C - 27/19) Pdc kW 4.04  
      power input kW 0.46  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-D Condition (20°C - 27/19)-=-Eerd 8.86  
    C Condition (25°C - 27/19) power input kW 0.70  
      Pdc kW 4.60  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-C Condition (25°C - 27/19)-=-Eerd 6.58  
    A Condition (35°C - 27/19) power input kW 2.96  
      Pdc kW 9.50  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-A Condition (35°C - 27/19)-=-Eerd 3.21  
    B Condition (30°C - 27/19) Pdc kW 7.00  
      power input kW 1.55  
      Seasonal efficiency (according to EN14825)-=-Cooling-=-B Condition (30°C - 27/19)-=-Eerd 4.50  
  Heating (Average climate) Annual energy consumption kWh 2,721.228  
    Pdesign kW 7.60  
    Required back up heating cap at design conditions kW 0.48  
    Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-Seasonal efficiency according to en14825 heating average climate scop a A  
    TBivalent Pdh (declared heating cap) kW 6.72  
      Power input kW 2.09  
      Tbiv (bivalent temperature) °C -7  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TBivalent-=-Copd declared cop 3.22  
    C Condition (7°C) Pdh (declared heating cap) kW 3.10  
      Power input kW 0.57  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-C Condition (7°C)-=-Copd declared cop 5.42  
    TOL Tol (temperature operating limit) °C -15  
      Pdh (declared heating cap) kW 7.79  
      Power input kW 3.70  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-TOL-=-Copd declared cop 2.11  
    A Condition (-7°C) Pdh (declared heating cap) kW 6.72  
      Power input kW 2.09  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-A Condition (-7°C)-=-Copd declared cop 3.22  
    D Condition (12°C) Pdh (declared heating cap) kW 3.53  
      Power input kW 0.55  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-D Condition (12°C)-=-Copd declared cop 6.38  
    B Condition (2°C) Power input kW 1.42  
      Pdh (declared heating cap) kW 5.16  
      Seasonal efficiency (according to EN14825)-=-Heating (Average climate)-=-B Condition (2°C)-=-Copd declared cop 3.64  
Cooling capacity Nom. kW 9.5 13.4
Pck (Crankcase heater mode) W 0.0  
Nominal efficiency Annual energy consumption kWh 1,480 (0.000)  
  Energy labeling Directive Heating A  
  Nominal efficiency-=-Cop 3.21 3.01
Heating Psb (Standby mode heating) W 7.0  
  Heating-=-Heating cdh degradation heating 0.25  
Heating capacity Nom. kW 10.8 15.5
Pto (Thermostat off) W 7.0  
Power input Cooling Nom. kW 2.96 4.45
  Heating Nom. kW 2.99 4.54
Cold season included Yes  
Notes EER/COP according to Eurovent 2012, for use outside EU only EER/COP according to Eurovent 2012, for use outside EU only
  Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load