Specifications Table for RZQG-L(8)Y1

RZQG71L8Y1B RZQG100L8Y1B RZQG125L8Y1B RZQG140L7Y1B
Dimensions Unit Height mm 990 1,430 1,430 1,430
    Width mm 940 940 940 940
    Depth mm 320 320 320 320
Weight Unit kg 80.0 101.0 101.0 101.0
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Operation range Cooling Ambient Min. °CDB -15.0 -15.0 -15.0 -15.0
      Max. °CDB 50.0 50.0 50.0 50.0
  Heating Ambient Min. °CWB -20.0 -20.0 -20.0 -20.0
      Max. °CWB 15.5 15.5 15.5 15.5
Sound power level Cooling dBA 64.0 66.0 67.0 69.0
  Heating dBA 64.0 66.0 67.0 69.0
Sound pressure level Cooling Nom. dBA 48 50 51 52
  Heating Nom. dBA 50 52 53 53
  Night quiet mode Level 1 dBA 43 45 45 45
Refrigerant Type   R-410A R-410A R-410A R-410A
  Charge kg 2.9 4.0 4.0 4.0
  Charge TCO2Eq 6.05 8.35 8.35 8.35
  GWP   2,087.5 2,087.5 2,087.5 2,087.5
Piping connections Liquid OD mm 9,52 9,52 9,52  
  Gas OD mm 15.9 15.9 15.9  
  Piping length OU - IU Max. m 50 75 75  
    System Equivalent m 70 90 90  
      Chargeless m 30 30 30  
  Additional refrigerant charge kg/m See installation manual See installation manual See installation manual  
  Level difference IU - OU Max. m 30.0 30.0 30.0  
    IU - IU Max. m 0.5 0.5 0.5  
Standard Accessories Tie-wraps 2 2 2 2
  Installation manual 1 1 1 1
Power supply Phase   3N~ 3N~ 3N~ 3N~
  Frequency Hz 50 50 50 50
  Voltage V 380-415 380-415 380-415 380-415
Current - 50Hz Maximum fuse amps (MFA) A 16 25 25  
Notes (1) - 3 with re-charging (1) - 3 with re-charging (1) - 3 with re-charging 3 with re-charging
  (2) - See separate drawings for electrical data (2) - See separate drawings for electrical data (2) - See separate drawings for electrical data See separate drawings for electrical data
  (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
  (4) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (4) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (4) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A
Piping connections Additional refrigerant charge kg/m       See installation manual
  Level difference IU - OU Max. m       30.0
    IU - IU Max. m       0.5