Specifications Table for 4MWXM-A9

4MWXM52A2V1B9
Dimensions Unit Height mm 734
    Width mm 974
    Depth mm 401
Weight Unit kg 60
Fan motor Speed Cooling Super low rpm 420
    Heating Super low rpm 420
Compressor Type   Hermetically sealed swing compressor
Operation range Cooling Ambient Min. °CDB -10
      Max. °CDB 46
Sound pressure level Cooling Nom. dBA 46
  Heating Nom. dBA 47
Refrigerant Type   R-32
  Charge kg 2.2
  Charge tCO2Eq 1.49
  GWP   675
Piping connections Piping length OU - IU Max. m 25 (1)
  Additional refrigerant charge kg/m 0.02 (for piping length exceeding 30m)
  Level difference IU - OU Max. m 15.0
    IU - IU Max. m 7.5
  Total piping length System Actual m 50
Standard Accessories Installation manual 1
  Drain cap 3
  Drain plug 1
  Reducer assembly 1
  Screw bag 1
Power supply Phase   1~
  Frequency Hz 50
  Voltage V 220-240
Notes (1) - For one room