Specifications Table for ACQ-D / AZQS-B(8)V1

ACQ71DV1 / AZQS71B2V1B ACQ100DV1 / AZQS100B8V1B ACQ125DV1 / AZQS125B8V1B ACQ140DV1 / AZQS140B8V1B
Cooling capacity Nom. kW 6.8 9.5 12.1 13.0
Space cooling SEER   5.70 5.50
  Annual energy consumption kWh/a 418 605
  Capacity Pdesign kW 6.80 9.50
  Energy efficiency class   A+ A
Space heating (Average climate) Capacity Pdesign kW 6.33 7.60
  SCOP/A   4.00 3.85
  Energy efficiency class   A A
  Annual energy consumption kWh/a 2,216 2,764
Nominal efficiency EER   3.31 3.21 3.10 3.21
  Annual energy consumption kWh 1,025 1,480 1,952 2,025
  COP   3.61 3.61 3.61 3.61
  Energy labeling Directive Cooling   A A B A
    Heating   A A A A
Heating capacity Nom. kW 7.50 10.80 13.5 15.5
Notes (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only
  (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load
    (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
    (4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 (4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 (4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2
    (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data
    (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases