| FFA35A2VEB / FFA35A2VEB / FFA35A2VEB / RZASG100M7Y1B | FFA50A2VEB / FFA50A2VEB / RZASG100M7Y1B | ||||
|---|---|---|---|---|---|
| Outdoor unit | RZASG100M7Y1B | RZASG100M7Y1B | |||
| Cooling capacity | Nom. | kW | 9.50 | 9.50 | |
| Heating capacity | Nom. | kW | 10.8 | 10.8 | |
| Space cooling | Energy efficiency class | A++ | A | ||
| Capacity | Pdesign | kW | 9.50 | 9.50 | |
| SEER | 6.24 | 5.49 | |||
| Annual energy consumption | kWh/a | 533 | 606 | ||
| Space heating (Average climate) | Energy efficiency class | A | A | ||
| Capacity | Pdesign | kW | 6.00 | 6.00 | |
| SCOP/A | 3.82 | 3.90 | |||
| Annual energy consumption | kWh/a | 2199 | 2154 | ||
| Notes | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. | |||
| (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. | ||||