Specifications Table for FXSN-A2

FXSN50A2VEB FXSN112A2VEB
Sound pressure level Heating At high fan speed dBA 38.0 42.0
    At low fan speed dBA 32.0 38.0
    At medium fan speed dBA 35.0 40.0
  Cooling At low fan speed dBA 31.0 34.0
    At high fan speed dBA 36.0 40.0
    At medium fan speed dBA 33.0 38.0
Standard Accessories Installation and operation manual 1 1
  Drain hose 1 1
  Metal clamp for drain hose 1 1
  Washer for hanger bracket 8 8
  Screws 40 40
  Insulation for fitting 2 2
  Sealing pad 5 5
  Clamps 4 4
Refrigerant GWP   1.0 1.0
  Type   R-744 R-744
Power input - 50Hz Cooling At high fan speed kW 0.186 0.388
  Heating At high fan speed kW 0.181 0.383
Cooling capacity Total capacity At high fan speed kW 5.60 12.50
Piping connections Liquid OD mm 9.52 9.52
    Type   Brazing-brazing connection Brazing-brazing connection
  Gas OD mm 12.7 12.7
    Type   Brazing-brazing connection Brazing-brazing connection
  Drain   VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm
Sound power level Cooling At high fan speed dBA 61 66
Air filter Type   Resin net Resin net
Dimensions Unit Width mm 700 1,400
    Depth mm 800 800
    Height mm 245 245
Casing Material   Galvanised steel plate Galvanised steel plate
  Colour   Not painted (galvanised) Not painted (galvanised)
Weight Unit kg 31.0 50.0
Fan External static pressure - 50Hz High Pa 150 150
  Air flow rate - 50Hz Cooling At high fan speed m³/min 15.2 36.0
      At low fan speed m³/min 11.0 26.0
Drain-up height mm 625 625
Heating capacity Total capacity At high fan speed kW 6.30 14.0
Current - 50Hz Maximum fuse amps (MFA) A 16 16
Power supply Phase   1~ 1~
  Name   VE VE
  Frequency Hz 50/60 50/60
  Voltage V 220-240/220 220-240/220
Notes (1) - The sound power level is an absolute value indicating the power which a sound source generates. (1) - The sound power level is an absolute value indicating the power which a sound source generates.
  (2) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (2) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (3) - Select wire size based on the value of MCA (3) - Select wire size based on the value of MCA
  (4) - Maximum allowable voltage range variation between phases is 2%. (4) - Maximum allowable voltage range variation between phases is 2%.
  (5) - Use a circuit breaker instead of a fuse. (5) - Use a circuit breaker instead of a fuse.
  (6) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere. (6) - MCA/MFA; MCA= 1,25 x FLA; MFA=< 4 x FLA; The next lower standard fuse rating is minimum 16 ampere.
  (7) - Contains fluorinated greenhouse gases (7) - Contains fluorinated greenhouse gases